NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
203
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
located in
inappropriat
e positions.
2.
The thermal
load power
is high or the
cooling
capacity is
insufficient.
3.
The ambient
temperature
exceeds the
upper
threshold.
4.
The high
temperature
alarm
threshold is
inappropriat
e.
5.
The value
detected by
the
temperature
sensor or
temperature
and
humidity
sensor is
different
from the
actual value.
6.
The chilled
water flow is
insufficient,
or the supply
water
temperature
is high.
7.
The chilled
water valve
is stuck or
faulty.
humidity
sensors.
2.
Add smart
cooling
products or
contact
Huawei
technical
support.
3.
Measure the
ambient
temperature.
Check
whether
other causes
exist if the
alarm
persists in a
long time
after startup.
4.
Adjust the
high
temperature
alarm
threshold.
5.
Calibrate or
replace the
temperature
sensor or
temperature
and
humidity
sensor.
6.
Check the
pressure and
temperature
of chilled
water.
7.
Maintain or
replace the
chilled water
valve.
A049-01
Supply air low
temperature
alarm
Warning
N/A
1.
The
temperature
sensors or
temperature
and
humidity
sensors are
located in
1.
Adjust the
positions of
the
temperature
sensors or
temperature
and
humidity