6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
176
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
system is
shut down.
2.
The SPD three-phase
detection board is faulty.
the working range.
2.
Replace the SPD
three-phase detection
board.
a035
Power
underfreque
ncy alarm
Major
An alarm is
triggered,
and the
system is
shut down.
1.
The power supply
frequency is below the
lower threshold.
2.
The SPD three-phase
detection board is faulty.
1.
The SPD three-phase
detection board is
faulty.
2.
Replace the SPD
three-phase detection
board.
a036
Power phase
loss
Major
N/A
1.
The power grid is unstable.
2.
The SPD (if configured)
may be faulty.
1.
Check the power grid.
2.
Maintain or replace
the surge protection
board.
a039
Control
point sensor
disabled
alarm
Major
An alarm is
triggered.
All the temperature sensors or
temperature and humidity
sensors at the control point are
disabled.
Enable the temperature
sensors or temperature
and humidity sensors at
the control point or
change the control point.
a042
Remote
shutdown
alarm
Critical An alarm is
triggered,
and the
system is
shut down.
1.
The remote shutdown dry
contact is triggered.
2.
The cables to the remote
shutdown dry contact are
loose or damaged.
1.
Check the status of the
remote shutdown dry
contact.
2.
Check the cables to
the remote shutdown
dry contact.
a043
Floor water
overflow
Critical An alarm is
triggered,
and the
system is
shut down.
1.
Water exists on the floor.
2.
The overflow sensor cable
is not properly connected.
3.
The water sensor is faulty.
1.
Check and clear the
water.
2.
Check the cable
connection to the
overflow sensor.
3.
Maintain or replace
the water sensor.
a044
Smoke
detected
Critical An alarm is
triggered,
and the
system is
shut down.
1.
Smoke is generated in the
equipment room.
2.
The cables to the smoke
sensor are loose or
damaged.
3.
The smoke sensor is faulty.
1.
Exhaust smoke in
equipment room and
reset the smoke
sensor.
2.
Check the cables to
the smoke sensor.
3.
Maintain or replace
the smoke sensor.
a045
Teamwork
networking
failed
Major
An alarm is
triggered,
and
teamwork
mode is
exited to
work in
1.
The DIP switch is set
incorrectly for teamwork.
2.
The teamwork cables are
loose or damaged.
3.
Any two smart cooling
product units have the same
1.
Set the DIP switch
correctly for
teamwork.
2.
Check the teamwork
cables.
3.
Change the addresses