NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
125
Menu
Parameter Description
Configuration Principle
Settings
(visible
for
V200R0
02
version)
g function
be set to
Enable
,
Disable
, or
Enabled when active power
.
electric humidifier will be
started when the ambient
humidity is lower than the
certain humidity range of the
humidity set point.
Disable
indicates that the electric
humidifier will not be started.
Enabled when active power
indicates that the electric
humidifier will be started when
the main power is active and
the ambient humidity is lower
than the certain humidity range
of the humidity set point.
Dehumidify
ing function
The dehumidifying function
can be set to
Enable
,
Disable
,
or
Enabled when active
power
.
Enable
indicates that the
dehumidification function will
be enabled when the ambient
humidity exceeds the certain
humidity range of the humidity
set point.
Disable
indicates
that the dehumidification
function will not be enabled.
Enabled when active power
indicates that the
dehumidification function will
be enabled when the main
power is active and the
ambient humidity exceeds the
certain humidity range of the
humidity set point.
T/H
sensor
(visible
for
V200R0
02
version)
Temperatur
e and
humidity
control type
Cold aisle
,
Hot aisle
,
Return
air
, or
Supply air
can be set as
required. The temperature and
humidity set points correspond
to the selected control type can
be set.
When the application
scenario is cold or hot aisle
containment, you are
advised to choose
Cold
aisle
if the cold aisle T/H
sensors are configured, and
choose
Supply air
if the
cold aisle T/H sensors are
not configured.
When the application
scenario is non-aisle
containment, you are
advised to choose
Return
air
, and choose
Cold aisle
if the cold aisle T/H sensors
are configured.
Hot aisle
is not
recommended.
Temperatur
e control
This parameter controls the
temperature inside the room or
Average value: Select
Average value
if the