NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
188
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
a220
Wizard
startup is in
progress
Warnin
g
N/A
Wizard startup in progress.
Wait until wizard startup
is complete or clear the
Wizard startup in
progress alarm manually
to exit wizard startup.
a225
Fresh air
damper
close fault
Major
N/A
The fresh air damper is faulty. Maintain or replace the
fresh air damper.
a226
Fresh air
damper
feedback
abnorm
Major
N/A
1.
The control cable to the
fresh air damper is not
properly connected.
2.
The fresh air damper is
faulty.
1.
Check the feedback
cable connection to
the fresh air damper.
2.
Maintain or replace
the fresh air damper.
a227
Fresh air
damper
feedback
fault
Major
N/A
1.
The control cable to the
fresh air damper is not
properly connected.
2.
The fresh air damper is
faulty.
1.
Check the feedback
cable connection to
the fresh air damper.
2.
Maintain or replace
the fresh air damper.
a228
Return air
damper
feedback
abnorm
Major
N/A
1.
The control cable to the
return air damper is not
properly connected.
2.
The return air damper is
faulty.
1.
Check the control
cable connection to
the return air damper.
2.
Maintain or replace
the return air damper.
a229
Return air
damper
feedback
fault
Major
N/A
1.
The control cable to the
return air damper is not
properly connected.
2.
The return air damper is
faulty.
1.
Check the control
cable connection to
the return air damper.
2.
Maintain or replace
the return air damper.
a230
Direct
free-cooling
plenum
open fault
Major
N/A
1.
The cables to the fresh and
return air dampers are not
properly connected.
2.
The fresh and return air
dampers are faulty.
1.
Check the cable
connections to the
fresh and return air
dampers.
2.
Maintain or replace
the fresh and return air
dampers.
a231
Direct
free-cooling
plenum
close fault
Major
N/A
1.
The cables to the fresh and
return air dampers are not
properly connected.
2.
The fresh and return air
dampers are faulty.
1.
Check the cable
connections to the
fresh and return air
dampers.
2.
Maintain or replace
the fresh and return air
dampers.
a232
Fresh air
filter
blocked
Warnin
g
N/A
1.
The fresh air filter is dirty
or blocked.
2.
The differential pressure
switch of the fresh air unit
1.
Maintain or replace
the fresh air filter.
2.
Replace the
differential pressure