NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
204
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
inappropriat
e positions.
2.
The thermal
load power
is low.
3.
The ambient
temperature
is below the
lower
threshold.
4.
The low
temperature
alarm
threshold is
inappropriat
e.
5.
The value
detected by
the
temperature
sensor or
temperature
and
humidity
sensor is
different
from the
actual value.
6.
The air
filters are
blocked.
7.
The chilled
water valve
is stuck or
faulty.
sensors.
2.
Contact
Huawei
technical
support.
3.
Measure the
ambient
temperature.
Check
whether
other causes
exist if the
alarm
persists in a
long time
after startup.
4.
Adjust the
low
temperature
alarm
threshold.
5.
Calibrate or
replace the
temperature
sensor or
temperature
and
humidity
sensor.
6.
Maintain or
replace the
air filters.
7.
Maintain or
replace the
chilled water
valve.
A050-01
Cold aisle high
temperature
alarm
Critical
N/A
1.
The
temperature
sensors or
temperature
and
humidity
sensors are
located in
inappropriat
e positions.
2.
The thermal
load power
is high or the
cooling
capacity is
1.
Adjust the
positions of
the
temperature
sensors or
temperature
and
humidity
sensors.
2.
Add smart
cooling
products or
contact
Huawei
technical