NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
96
No.
Definition
Function
alarm if a smoke or water alarm occurs.
When
DO associated alarm
is set to
Critical&major
ALM
, the smart cooling product issues an alarm if a
critical alarm occurs.
Normal Open signal dry contact output. Connection to an
outdoor device is forbidden.
4
Common alarm 2
terminal
When
DO associated alarm
is set to
Critical&major
ALM
, the smart cooling product issues an alarm if a major
alarm occurs.
Normal Open signal dry contact output. Connection to an
outdoor device is forbidden.
5
Water leakage
sensor terminal
Terminals X2.9 and X2.10 are connected to the water
leakage sensor. If water leaks, the smart cooling product
generates an alarm.
6
Direct free-cooling
plenum YV1
terminal
Terminals X2.11–X2.14 are connected to the direct
free-cooling plenum actuator to open and close the direct
free-cooling plenum. The direct free-cooling plenum is
used together with return air damper YV2. The fresh air
function needs to be enabled.
7
Return air damper
YV2
terminal/motorized
damper YV3
terminal
Return air damper YV2: Terminals X2.15–X2.18 are
connected to the return air damper actuator to open and
close the return air damper. The return air damper is
used together with the direct free-cooling plenum. The
fresh air function needs to be enabled.
Motorized damper YV3: Terminals X2.15–X2.18 are
connected to the motorized damper actuator. The
motorized damper needs to be enabled.
Note: Functions of the direct free-cooling plenum and
motorized damper are mutually exclusive.
8
Differential pressure
sensor terminal
Terminals X2.19–X2.21 connect to the differential pressure
sensor. The fan works in pressure control mode based on
the data detected by the differential pressure sensor.
9
Water valve
actuator terminal
Terminals X2.22–X2.25 are connected before delivery, and
do not need to be connected onsite.
10
Reserved 24 V DC
terminal
Terminal X2.26 is reserved.
11
Differential pressure
switch terminal of
the fresh air filter
Terminals X2.27–X2.28 are connected to the differential
pressure switch of the fresh air filter to generate alarms
when the fresh air filter is blocked.
Note: The terminal applies only to downflow units.