NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
126
Menu
Parameter Description
Configuration Principle
mode
aisles based on the
Average
value
,
Max value
, or
Min
value
of the temperatures
collected by each sensor.
temperature is to be
controlled based on the
averaged data value
collected by the collector.
Max value: Select
Max
value
if the temperature is
to be controlled based on
the maximum data value
collected by the collector.
Min value: Select
Min
value
if the temperature is
to be controlled based on
the minimum data value
collected by the collector.
Temperatur
e setpoint
After the Temperature and
humidity control type and the
temperature value under this
type are set, the device
conducts cooling or heating
based on the settings.
Set this parameter as required.
Return air temperature:
26–35°C recommended
Supply air temperature:
18–24°C recommended
Cold aisle temperature:
18–24°C recommended
Hot aisle temperature:
26–35°C recommended
Humidity
setpoint
After the Temperature and
humidity control type and the
humidity value under this type
are set, the device conducts
humidifying or dehumidifying
based on the settings.
Set this parameter as required.
40%–60% RH recommended
Cold aisle
sensor 1
Cold aisle
sensor 2
Cold aisle
sensor 3
Cold aisle
sensor 4
Cold aisle
sensor 5
The sensors in cold aisles can
be set to
Enable
or
Disable
.
The cold aisle sensors outside
the cabinet need to be enabled
when they are installed.
Hot aisle
sensor 1
Hot aisle
sensor 2
Hot aisle
sensor 3
Hot aisle
The sensors in hot aisles can be
set to
Enable
or
Disable
.
The hot aisle sensors outside
the cabinet need to be enabled
when they are installed.