6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
219
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
fan is shut
down.
damaged.
2.
The indoor
fan is faulty.
fan.
2.
Maintain or
replace the
indoor fan.
A26B-02
Indoor fan 1
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.
Indoor fan 2
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.
Indoor fan 3
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.
Indoor fan 4
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.
A26B-04
Indoor fan 1
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The cables
to the indoor
fan are loose
or damaged.
2.
The indoor
fan is faulty.
1.
Check the
cables to the
indoor fan.
2.
Maintain or
replace the
indoor fan.
Indoor fan 2
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The cables
to the indoor
fan are loose
or damaged.
2.
The indoor
fan is faulty.
1.
Check the
cables to the
indoor fan.
2.
Maintain or
replace the
indoor fan.
Indoor fan 3
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The cables
to the indoor
fan are loose
or damaged.
2.
The indoor
fan is faulty.
1.
Check the
cables to the
indoor fan.
2.
Maintain or
replace the
indoor fan.