NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
222
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
the indoor
fan are
faulty.
controlling
the indoor
fan.
A278-04
Chilled water
valve fault
Major
An alarm is
triggered.
1.
The cables
to the chilled
water valve
are loose or
damaged.
2.
The chilled
water valve
is faulty.
1.
Check
cables to the
chilled water
valve.
2.
Maintain or
replace the
chilled water
valve.
A278-08
Chilled water
valve fault
Major
An alarm is
triggered.
1.
The cables
to the chilled
water valve
are loose or
damaged.
2.
The chilled
water valve
is faulty.
1.
Check the
control cable
connection
to the chilled
water valve.
2.
Maintain or
replace the
chilled water
valve.
A279-01
Motorized
damper fault
Critical
An alarm is
triggered, and
the smart
cooling product
is shut down.
1.
The control
cable to the
air damper is
loose or
damaged.
2.
The air
damper is
faulty.
1.
Check the
control cable
connection
to the air
damper.
2.
Maintain or
replace the
air damper.
A279-02
Motorized
damper fault
Critical
An alarm is
triggered.
The air damper
is faulty.
Maintain or
replace the air
damper.
Fresh air
damper fault
Critical
An alarm is
triggered.
The air damper
is faulty.
Maintain or
replace the air
damper.
A279-04
Motorized
damper fault
Critical
An alarm is
triggered.
1.
The
feedback
cable to the
air damper is
loose or
damaged.
2.
The air
damper is
faulty.
1.
Check the
feedback
cable
connection
to the air
damper.
2.
Maintain or
replace the
air damper.
Fresh air
damper fault
Critical
An alarm is
triggered.
1.
The
feedback
cable to the
air damper is
loose or
1.
Check the
feedback
cable
connection
to the air