NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
47
For a single-door and double-door cabinet, remove the four bolts from both sides.
Figure 3-14
Removing the bolts that secure the cabinet and the pallet
Step 3
(Only applicable to downflow units) Install the fan maintenance baffle plate at the front door.
Step 4
Close the front door and reinstall the rear door.
----End
3.4.4 (Optional) Cabinet Assembly (Applicable only to Downflow
Units with Four Doors)
Context
Operations should be conducted in a spacious and safe environment.
After the cables are connected, mark the terminals and bind them along the cabinet beam
using cable ties.
Ensure that nitrogen is completely exhausted from the exhaust valves of all modules.
Procedure
Step 1
Remove the side protection cardboards and rear door panels of module 2 and module 3. Open
the front doors of module 2 and module 3, and remove the fan protective cover.