NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
104
Figure 3-76
Connecting the water leakage sensor for a downflow unit
Step 3
Connect the other end of the two-core cable to terminals X2.9 and X2.10 on the terminal
block.
Step 4
Secure cables to the water leakage sensor using cable ties.
----End
3.6.7 (Optional) Connecting the Gravity Damper (Applicable To
Upflow Units)
For details about how to connect the gravity damper, see the documents delivered with it.
3.6.8 (Optional) Connecting the Motorized Damper (Applicable
To Downflow Units)
After powering on the NetCol8000, choose
Settings
>
System Settings
>
Common Settings
,
and set
Motorized Damper
to
Enable
.