NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
185
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
Alarm
dropped and is jammed.
3.
The humidifier float
interconnection terminals
are abnormal.
4.
The water inlet solenoid
valve cannot open.
5.
Cables of the water inlet
solenoid valve are not
properly connected.
2.
Verify that the
humidifier float can
float and drop
properly.
3.
Verify that the
humidifier float
interconnection
terminals are properly
connected.
4.
Verify that water
flows into the
humidifier pan from
the water inlet pipe of
the humidifier.
5.
Verify that cables of
the water inlet
solenoid valve are
properly connected.
NOTE
After the fault is rectified,
click
Clear
on the alarm
page to manually clear the
alarm.
a193
Supply-air
Pressure diff
invalid
Major
An alarm is
triggered.
1.
The differential pressure
sensor cable is not properly
connected.
2.
The pressure tube for the
differential pressure sensor
is reversely connected.
3.
The differential pressure
sensor is faulty.
1.
Check the cable
connection to the
differential pressure
sensor.
2.
Check the tube
connection to the
differential pressure
sensor.
3.
Maintain or replace
the differential
pressure sensor.
a196
CW valve
feedback
fault alarm
Major
An alarm is
triggered.
1.
The cables to the chilled
water valve are loose or
damaged.
2.
The chilled water valve is
faulty.
1.
Check cables to the
chilled water valve.
2.
Maintain or replace
the chilled water
valve.
a197
Motorized
damper on
fault
Critical N/A
1.
The control cable to the
motorized damper is not
properly connected.
2.
The motorized damper is
faulty.
1.
Check the feedback
cable connection to
the motorized damper.
2.
Maintain or replace
the motorized damper.
a198
Motorized
damper off
fault
Warnin
g
N/A
The motorized damper is
faulty.
Reconnect the motorized
damper cable.