NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
236
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
board.
A282-01
Power phase
sequence
abnormal
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the main
power or single
power is
supplied.
1.
The power
grid is
unstable.
2.
The SPD
and voltage
detection
board may
be faulty if it
is
configured.
3.
The cables
to the
primary
power
supply or
compressor
drive are
loose or
damaged.
1.
Check the
power grid.
2.
Maintain or
replace the
SPD and
voltage
detection
board.
3.
Check the
cable
connection
to the
primary
power
supply and
compressor
drive.
Backup power
phase sequence
abnormal
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the
standby power
is supplied.
1.
The power
grid is
unstable.
2.
The SPD
and voltage
detection
board may
be faulty if it
is
configured.
3.
The cables
to the
primary
power
supply or
compressor
drive are
loose or
damaged.
1.
Check the
power grid.
2.
Maintain or
replace the
SPD and
voltage
detection
board.
3.
Check the
cable
connection
to the
primary
power
supply and
compressor
drive.
A286-01
Auxiliary power
fault
Major
N/A
The auxiliary
power supply is
faulty.
Maintain or
replace the
auxiliary power
supply module.
A286-02
Auxiliary power
fault
Major
N/A
The auxiliary
power supply is
faulty.
Maintain or
replace the
auxiliary power
supply module.