NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
198
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
and
humidity
sensor is set
incorrectly.
3.
The
temperature
and
humidity
sensor is
faulty.
4.
The
communicati
ons port of
the main
control
board is
faulty.
sensor
correctly.
3.
Maintain or
replace the
temperature
and
humidity
sensor.
4.
Maintain or
replace the
main control
board.
Return air
damper 1
temp/humid
sensor comm
failed
Major
N/A
1.
The cables
to the
temperature
and
humidity
sensor are
loose or
damaged.
2.
The DIP
switch of the
temperature
and
humidity
sensor is set
incorrectly.
3.
The
temperature
and
humidity
sensor is
faulty.
4.
The
communicati
ons port of
the main
control
board is
faulty.
1.
Check the
cables to the
temperature
and
humidity
sensor.
2.
Set the DIP
switch of the
temperature
and
humidity
sensor
correctly.
3.
Maintain or
replace the
temperature
and
humidity
sensor.
4.
Maintain or
replace the
main control
board.
A018-01
Indoor fan 1
exceed runtime
alarm
Warning
An alarm is
triggered.
1.
The
accumulated
runtime of
the indoor
fan exceeds
the alarm
1.
Maintain or
replace the
indoor fan
and clear the