NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
132
Parameter
Description
Configuration Principle
difference setpoint
pressure difference control.
Air-side difference pressure
sensor type
Sets the measuring range for
the air side differential
pressure sensor.
There is no default value.
Set it to 0~500 Pa.
Min indoor fan speed
Sets the minimum speed for
the indoor fan.
The default value is 60%.
You are advised not to
change the value.
Max indoor fan speed
Sets the maximum speed for
the indoor fan.
The default value is 100%.
You are advised not to
change the value.
----End
4.4.3 Setting Teamwork Control Parameters
Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
smart cooling products as follows:
Teamwork group no.: Group the smart cooling products in adjacent areas as one, that is,
assign one teamwork group number for them. At most four teamwork groups can be
assigned (1–4).
Teamwork unit address: The address for the smart cooling product in the same group
cannot be the same (address range: 1–32). The smart cooling product with minimum
address is the master one that collects, processes, and delivers data.
Context
The parameters in this section are for reference only. Set actually parameter values as
required.
Procedure
Step 1
On the home screen, tap
>
Teamwork Settings
, to enter
Teamwork Settings
page, as