Check
Item
Expected Result
Actual Result
The hose clamps and cable ties of the condensate
water pipe are reliably secured.
□Passed □Failed
The water inlet and outlet pipes are properly
installed and secured, without leaks.
□Passed □Failed
The water inlet and outlet pipes are routed
smoothly, without bends.
□Passed □Failed
The water outlet pipe has appropriate gradients
(1:100 is recommended).
□Passed □Failed
Cable
connections
The power voltage is the same as the rated voltage
on the nameplate of the unit.
□Passed □Failed
Cables are intact.
□Passed □Failed
No open or short circuits, or incorrect connections
occur in electrical loops.
□Passed □Failed
Power cables, signal cables, and communications
cables have been connected.
□Passed □Failed
The rated values of circuit breakers are correct.
□Passed □Failed
Control cables are properly connected.
□Passed □Failed
All cables, connectors, and bolts are secured.
□Passed □Failed
(Optional)
Pressure
diff sensor
The pressure tube is secured by cable ties.
□Passed □Failed
There is no foreign matter in pressure tubes. The
pressure tubes show no obvious bends.
□Passed □Failed
The pressure diff sensor is secured reliably and
steadily.
□Passed □Failed
Cables are connected reliably and steadily.
□Passed □Failed
(Optional)
Motorized
Damper/Gr
avity
Damper
The damper and cabinet are secured reliably and
steadily by bolts as required.
□Passed □Failed
(Applicable to motorized damper) Cables of the
damper actuator are connected reliably and steadily.
□Passed □Failed
(Optional)
Water
leakage
sensor
Cables to the water leakage sensor are connected
correctly and securely.
□Passed □Failed
(Optional)
Cap
The cap and cabinet are secured reliably and
steadily as required.
□Passed □Failed
(Optional)
Direct
free-coolin
The direct free-cooling plenum and cabinet are
secured reliably and steadily as required.
□Passed □Failed
The actuator is reliably and securely connected.
□Passed □Failed