NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
114
Figure 3-85
Connecting cables
Step 5
Install the fan maintenance baffle plate.
----End
3.6.12 (Optional) Installing a Cap (Applicable to Upflow Units)
Prerequisites
Before installing the cap, attach the thermal insulation foam in the accessories to the top beam
of the smart cooling product, and ensure that the reserved holes in the thermal insulation foam
are aligned with the holes in the beam. Check that the cap is intact and free from scratches,
that the sheet metal is not bent, and that the screws are secure.
Context
Adjust the shutter angle as required. Normally, keep the shutter horizontal. To specifically
cool the near-end devices, you can adjust the shutter angle to some degrees downward so that