NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
206
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
3.
The ambient
temperature
exceeds the
upper
threshold.
4.
The high
temperature
alarm
threshold is
inappropriat
e.
5.
The value
detected by
the
temperature
sensor or
temperature
and
humidity
sensor is
different
from the
actual value.
6.
The chilled
water flow is
insufficient,
or the supply
water
temperature
is high.
7.
The chilled
water valve
is stuck or
faulty.
3.
Measure the
ambient
temperature.
Check
whether
other causes
exist if the
alarm
persists in a
long time
after startup.
4.
Adjust the
high
temperature
alarm
threshold.
5.
Calibrate or
replace the
temperature
sensor or
temperature
and
humidity
sensor.
6.
Check the
pressure and
temperature
of chilled
water.
7.
Maintain or
replace the
chilled water
valve.
A077-02
Indoor fan 1
fault
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.
Indoor fan 2
fault
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.
Indoor fan 3
fault
Major
An alarm is
triggered, and
the
corresponding
The indoor fan
is faulty.
Maintain or
replace the
indoor fan.