NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
181
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
threshold is inappropriate.
4.
The temp displayed is
different from the actual
temp.
humidity alarm
threshold.
4.
Calibrate or replace
the abnormal sensors.
a096
Supply-wate
r
temperature
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature sensor are
loose or damaged.
2.
The temperature sensor is
faulty.
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature
sensor.
a097
Supply-wate
r high
temperature
alarm
Major
An alarm is
triggered.
1.
The temperature of chilled
water is higher than the
supply water high
temperature alarm
threshold.
2.
The supply water high
temperature alarm threshold
is inappropriate.
3.
The supply water
temperature displayed is
different from the actual
temperature.
1.
Check the temperature
of supplied chilled
water.
2.
Adjust the supply
water high
temperature alarm
threshold.
3.
Calibrate or replace
the supply water
temperature sensor.
a098
Supply-wate
r LT
Warnin
g
An alarm is
triggered.
1.
The temperature of chilled
water is lower than the
supply water low
temperature alarm
threshold.
2.
The supply water low
temperature alarm threshold
is inappropriate.
3.
The supply water
temperature displayed is
different from the actual
temperature.
1.
Check the temperature
of supplied chilled
water.
2.
Adjust the supply
water low temperature
alarm threshold.
3.
Calibrate or replace
the supply water
temperature sensor.
a099
Return-wate
r temp
invalid
Major
An alarm is
triggered.
1.
The cables to the
temperature sensor are
loose or damaged.
2.
The temperature sensor is
faulty.
1.
Check the cables to
the temperature
sensor.
2.
Maintain or replace
the temperature
sensor.
a101
CW valve
abnormal
feedback
Warnin
g
An alarm is
triggered.
1.
The cables to the chilled
water valve are loose or
damaged.
2.
The chilled water valve is
faulty.
1.
Check the control
cable connection to
the chilled water
valve.
2.
Maintain or replace
the chilled water
valve.