NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
168
6.2 Monthly Maintenance
This section describes routine maintenance items for an indoor unit. Record maintenance
results in the table after a maintenance item is complete.
Table 6-1
Monthly maintenance
Maintenance
Item
Operation
Troubleshooting
Air filter
Check that the air filter is
clean and not blocked.
Clean the air filter.
Check that the air filter is not
damaged or distorted.
Replace the air filter (It is recommended
that an air filter should be replaced every
6 months).
Indoor fan
Check that the indoor fan
guard is not distorted.
Repair or replace the fan guard.
Check that the indoor fan
blades are intact.
Replace the fan.
Check that no foreign matter
exists in the fan.
Clear foreign matter.
Check that the indoor fan
generates no abnormal sound
during operation, such as
metal friction sound and
harsh noises.
Clear foreign matter and check that
screws securing the fan are tightened.
Check that the screws on the
indoor fan are not loose or
distorted.
Tighten or replace the screws.
Water pan
water pan is not blocked.
Clean the water pan.
Wet film
humidifier
Check that the humidifier
float has no scale.
Clean up the scale from the humidifier
float.
Check that the humidifier
float functions properly.
Repair or replace the humidifier float.
Check that the wet film and
humidifier water pan are
clean and have no scale.
Wash the wet film and humidifier water
pan with clean water. If there is serious
water scale, replace the wet film.
Check that no operating
overtime alarm is generated
on the wet film humidifier.
Replace the wet film humidifier (It is
recommended that an air filter should be
replaced every 12 months).
Check that the upstream filter
of the humidifier water pump
is not dirty or blocked.
Clean or replace the filter.
Check that the upstream filter
of the humidifier water pump
Replace the filter.