NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
190
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
Supply water
temperature
sensor fault
Major
An alarm is
triggered.
1.
The cables
to the
temperature
sensor are
loose or
damaged.
2.
The
temperature
sensor is
faulty.
1.
Check the
cables to the
temperature
sensor.
2.
Maintain or
replace the
temperature
sensor.
Return water
temperature
sensor fault
Major
An alarm is
triggered.
1.
The cables
to the
temperature
sensor are
loose or
damaged.
2.
The
temperature
sensor is
faulty.
1.
Check the
cables to the
temperature
sensor.
2.
Maintain or
replace the
temperature
sensor.
A002-01
Return air high
temperature
alarm
Critical
N/A
1.
The
temperature
sensors or
temperature
and
humidity
sensors are
located in
inappropriat
e positions.
2.
The thermal
load power
is high or the
cooling
capacity is
insufficient.
3.
The ambient
temperature
exceeds the
upper
threshold.
4.
The high
temperature
alarm
threshold is
inappropriat
e.
5.
The value
detected by
the
1.
Adjust the
positions of
the
temperature
sensors or
temperature
and
humidity
sensors.
2.
Add smart
cooling
products or
contact
Huawei
technical
support.
3.
Measure the
ambient
temperature.
Check
whether
other causes
exist if the
alarm
persists in a
long time
after startup.
4.
Adjust the
high
temperature