NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
69
----End
3.5.2.2 Downflow
3.5.2.2.1 Bottom Pipe Routing
Context
Tools: 75# open-end wrench, 36# open-end wrench, 18# pipe wrench, sealant (used for
pasting thermal insulation foam), screw thread sealant
Procedure
Step 1
Remove the baffle plate at the bottom of the cabinet, and knock off the U-shaped hole in the
baffle plate, as shown by (1) in
Connect pipes and then wrap thermal insulation foam around the whole pipeline.
Based on the hardening property of yellow adhesive, inject water and preserve the
pressureat least 8 hours after an adapter is connected.
Step 2
To avoid deforming the pipe, use a 75# open-end wrench to fix the pipe nut, use a 36#
open-end wrench to fix the plug, and then remove the plug, as shown by (2) in
Step 3
Apply thread sealant evenly on the joints of external screw threads, and install the pipes from
inside out, as shown by (3) in
Step 4
Use a 75# open-end wrench and 18# pipe wrench to fix the pipe, as shown by (4) in
Step 5
Install the pipe baffle plate at the bottom of the cabinet, and wrap the pipe with thermal
insulation foam, as shown by (5) in