Figure 3-78
Downflow
The T/H sensors inside the cabinet are secured at the return air side and their IN ports are connected
to the main control board. When connecting the T/H sensors outside the cabinet, connect the OUT
port of one T/H sensor inside the cabinet to the IN port of the next T/H sensor outside the cabinet.
Connect all T/H sensors in series in this way.
The T/H sensors should be 1.5 m above the ground (33 U).
Each smart cooling product supports a maximum of three T/H sensors in the cold and hot aisles
respectively.
Step 2
Set the DIP switches of T/H sensors.
shows a T/H sensor.
to set the DIP switches for T/H sensors.
Figure 3-79
DIP switches