NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
180
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
6.
Maintain or replace
the air filters.
7.
Maintain or replace
the chilled water
valve.
a092
Hot aisle
low
temperature
alarm
Warnin
g
An alarm is
triggered.
1.
The temperature sensors or
temperature and humidity
sensors are located in
inappropriate positions.
2.
The thermal load power is
low.
3.
The ambient temperature is
below the lower threshold.
4.
The low temperature alarm
threshold is inappropriate.
5.
The value detected by the
temperature sensor or
temperature and humidity
sensor is different from the
actual value.
6.
The air filters are blocked.
7.
The chilled water valve is
stuck or faulty.
1.
Adjust the positions of
the temperature
sensors or temperature
and humidity sensors.
2.
Measure the ambient
temperature. Check
whether other causes
exist if the alarm
persists in a long time
after startup.
3.
Measure the ambient
temperature.
4.
Adjust the low
temperature alarm
threshold.
5.
Calibrate or replace
the temperature sensor
or temperature and
humidity sensor.
6.
Maintain or replace
the air filters.
7.
Maintain or replace
the chilled water
valve.
a093
High
humidity
Warnin
g
An alarm is
triggered.
1.
The load is low.
2.
The ambient humidity
exceeds the upper
threshold.
3.
The temperature and
humidity sensor is not
installed in a proper
position.
4.
The high humidity alarm
threshold is inappropriate.
5.
The value detected by the
temperature and humidity
sensor is different from the
actual value.
1.
Contact Huawei
technical support.
2.
Measure the ambient
humidity.
3.
Adjust the position of
the temperature and
humidity sensor.
4.
Adjust the high
humidity alarm
threshold.
5.
Calibrate or replace
the temperature and
humidity sensors.
a094
Low
humidity
Warnin
g
An alarm is
triggered.
1.
The ambient humidity is
low.
2.
The T/H sensors are located
in inappropriate position.
3.
The low humidity alarm
1.
Check the ambient
humidity.
2.
Adjust the position of
the T/H sensors.
3.
Adjust the low