6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
174
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
a023
Electric
heater high
temperature
alarm
Major
An alarm is
triggered.
1.
The cables to the
temperature switch are
loose or damaged.
2.
The temperature switch is
faulty.
3.
The electric heater is faulty.
1.
Check the cables to
the temperature
switch.
2.
Maintain or replace
the temperature
switch.
3.
Replace the electric
heater.
a024
Electric
heater
exceed
runtime
alarm
Warnin
g
An alarm is
triggered.
The accumulated runtime of
the electric heater exceeds the
alarm threshold.
Maintain or replace the
electric heater and clear
the accumulated runtime.
a025
Air filter
blocked
Warnin
g
An alarm is
triggered,
and the
electric
heater and
humidifier of
the smart
cooling
product are
shut down.
1.
Air filters are blocked.
2.
The differential press
switch is faulty.
3.
The differential press
switch is set
inappropriately.
4.
The pressure inlet tube of
the differential pressure
switch is blocked or
disconnected.
5.
The cables to the
differential press switch are
loose or damaged.
6.
The motorized damper is
faulty.
7.
(Applicable to motorized
damper) The motorized
damper is disabled.
1.
Maintain or replace
the air filters.
2.
Replace the
differential press
switch.
3.
Adjust the threshold
of the differential
press switch.
4.
Maintain or replace
the press tube.
5.
Maintain or replace
the press tube.
6.
Maintain or replace
the motorized damper.
7.
(Applicable to
motorized damper)
Enable the motorized
damper.
NOTE
After the fault is rectified,
click
Clear
on the alarm
page to manually clear the
alarm.
a026
Air filter
exceed
runtime
Warnin
g
An alarm is
triggered.
The accumulated runtime of
the air filter exceeds the alarm
threshold.
Maintain or replace the
air filter and clear the
accumulated runtime.
a027
Power loss
alarm
Warnin
g
An alarm is
triggered.
The supply power is cut off.
If pwr fail ocurs on pwr
systm, no maint needed.
If it ocurs other place,
check the cable.
a028
Power AB
overvoltage
Major
An alarm is
triggered,
and the
1.
The power supply voltage
exceeds the upper
threshold.
1.
Check the power
supply voltage, and
ensure that the voltage
is within the operating