3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
81
3.6 Cable Connections
3.6.1 Precautions
Connections of all power cables, control cables, and ground cables must comply with the
local electrical code, and the cable specifications should comply with the local cabling
specifications.
For details about the current in full load, see the NetCol8000-C nameplate.
Requirements for the main power supply: 380–480 V AC, 3 Ph, 50 Hz/60 Hz for single
power supply; 380–415 V AC, 3 Ph, 50 Hz/60 Hz for dual power supplies; N wire not
required.
Only trained and qualified personnel are allowed to connect cables.
Before connecting cables, use a voltmeter to measure the input power voltage and ensure
that the power supply is off.
All the NetCol8000-Cs are safely grounded before being powered on.
Keep cables away from the fans and copper pipes. Otherwise, take protective measures.
Make sure that all cables are connected properly.
Bind the signal cables and power cables separately with the spacing of 50 mm
in-between.
3.6.2 Positions of Electric Ports
After opening the front door, you can see the connection box, as shown in the following
figure.