6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
220
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
Indoor fan 4
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The cables
to the indoor
fan are loose
or damaged.
2.
The indoor
fan is faulty.
1.
Check the
cables to the
indoor fan.
2.
Maintain or
replace the
indoor fan.
A272-01
Teamwork
networking
abnormal alarm
Warning
An alarm is
triggered, and
teamwork mode
is exited to
work in
standalone
mode.
1.
The DIP
switch on
the main
control
board is set
incorrectly
for
teamwork.
2.
The
teamwork
cables are
loose or
damaged.
3.
Any two
smart
cooling
product units
have the
same
address.
4.
No smart
cooling
product unit
is configured
as the master
unit.
5.
The master
unit is
powered off.
6.
The software
versions of
the smart
cooling
products in
the group
are
inconsistent.
7.
The sensor
that
corresponds
to the
temperature
and
humidity
1.
Set the DIP
switch
correctly for
teamwork.
2.
Check the
teamwork
cables.
3.
Change the
addresses of
the smart
cooling
product
units.
4.
Configure
one smart
cooling
product unit
as the master
unit.
5.
Power on
the master
unit, or
configure
another unit
as the master
unit.
6.
Upgrade the
smart
cooling
product
software by
referring to
the section
that
describes the
mapping
between the
software and
the
teamwork
versions in
the upgrade
guide.
7.
Enable the