NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
209
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
Indoor fan 4
fault
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan ground
cable is
loose or
damaged.
2.
The indoor
fan is faulty.
1.
Check the
ground cable
connection
to the indoor
fan.
2.
Maintain or
replace the
indoor fan.
A080-01
CW valve
exceed runtime
alarm
Warning
An alarm is
triggered.
The
accumulated
runtime of the
chilled water
valve exceeds
the alarm
threshold.
Maintain or
replace the
chilled water
valve and clear
the accumulated
runtime.
A091-01
Cold aisle low
temperature
alarm
Warning
N/A
1.
The
temperature
sensors or
temperature
and
humidity
sensors are
located in
inappropriat
e positions.
2.
The thermal
load power
is low.
3.
The ambient
temperature
is below the
lower
threshold.
4.
The low
temperature
alarm
threshold is
inappropriat
e.
5.
The value
detected by
the
temperature
sensor or
temperature
and
humidity
sensor is
different
from the
1.
Adjust the
positions of
the
temperature
sensors or
temperature
and
humidity
sensors.
2.
Contact
Huawei
technical
support.
3.
Measure the
ambient
temperature.
Check
whether
other causes
exist if the
alarm
persists in a
long time
after startup.
4.
Adjust the
low
temperature
alarm
threshold.
5.
Calibrate or
replace the
temperature
sensor or
temperature
and