NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
111
Figure 3-82
Connecting cables
----End
3.6.11.2 Connecting a Downflow Differential Pressure Sensor
Prerequisites
The PU hoses for connecting the differential pressure sensor are ready.
The hoses and cables are bound along the routes.
Context
The pressure tube at the air return side needs to be bound to the top cabinet beam
horizontally. If a blocked damper is configured, route the pressure tube through the hole
reserved in the damper enclosure frame, and bind the pressure tube to the cable bridge
inside the damper enclosure frame.
After powering on the NetCol8000, choose
Settings
>
System Settings
>
Common
Settings
, and set
Air-side difference pressure sensor type
to
0~500Pa
.
Procedure
Step 1
Secure the differential pressure sensor inside the cabinet using two M3 screws, with the
pressure inlet tube port facing downwards.