NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
216
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
loose or
damaged.
3.
The water
pump is
faulty.
4.
The water
pump races
due to a
liquid level
detection
fault.
5.
The water
pump is
blocked.
the water
pump cables
are properly
connected.
3.
Replace the
water pump.
4.
Rectify the
liquid level
detection
fault.
5.
Replace the
water pump.
A180-01
Humidifier
exceed runtime
alarm
Warning
N/A
The
accumulated
runtime of the
wet film of the
humidifier
exceeds the
alarm threshold.
Maintain or
replace the wet
film of the
humidifier and
clear the
accumulated
runtime.
A181-01
Humidifier
pump exceed
runtime alarm
Warning
N/A
The
accumulated
runtime of the
water pump
exceeds the
alarm threshold.
Maintain or
replace the
water pump and
clear the
accumulated
runtime.
A182-01
Water supply
abnormal alarm
Major
An alarm is
triggered, and
the humidifier is
shut down.
1.
The water
supply is
insufficient.
2.
The
humidifier
float has
dropped and
is jammed.
3.
The
humidifier
float
interconnecti
on terminals
are
abnormal.
4.
The water
inlet
solenoid
valve cannot
open.
5.
The cables
to the water
1.
Verify that
water supply
to the
humidifier is
normal.
2.
Verify that
the
humidifier
float can
float and
drop
properly.
3.
Verify that
the
humidifier
float
interconnecti
on terminals
are properly
connected.
4.
Verify that
water flows