NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
218
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
down.
Indoor fan 4
blocked alarm
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan blade is
stuck.
2.
The indoor
fan is faulty.
1.
Clear the
blockage.
2.
Maintain or
replace the
indoor fan.
A220-01
Wizard startup
is in progress
Warning
An alarm is
triggered.
Wizard startup
is in progress.
Wait until
wizard startup is
complete or
clear the Wizard
startup in
progress alarm
manually to exit
wizard startup.
A242-01
Manual
shutdown alarm
Major
An alarm is
triggered, and
the smart
cooling product
is shut down.
The smart
cooling product
is shut down via
the LCD or
NetEco.
Restart the
smart cooling
product via the
LCD or NetEco.
A26B-01
Indoor fan 1
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan ground
cable is
loose or
damaged.
2.
The indoor
fan is faulty.
1.
Check the
ground cable
connection
to the indoor
fan.
2.
Maintain or
replace the
indoor fan.
Indoor fan 2
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan ground
cable is
loose or
damaged.
2.
The indoor
fan is faulty.
1.
Check the
ground cable
connection
to the indoor
fan.
2.
Maintain or
replace the
indoor fan.
Indoor fan 3
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
fan is shut
down.
1.
The indoor
fan ground
cable is
loose or
damaged.
2.
The indoor
fan is faulty.
1.
Check the
ground cable
connection
to the indoor
fan.
2.
Maintain or
replace the
indoor fan.
Indoor fan 4
power supply
abnormal
Major
An alarm is
triggered, and
the
corresponding
1.
The indoor
fan ground
cable is
loose or
1.
Check the
ground cable
connection
to the indoor