NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
199
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
threshold.
runtime.
Indoor fan 2
exceed runtime
alarm
Warning
An alarm is
triggered.
1.
The
accumulated
runtime of
the indoor
fan exceeds
the alarm
threshold.
1.
Maintain or
replace the
indoor fan
and clear the
accumulated
runtime.
Indoor fan 3
exceed runtime
alarm
Warning
An alarm is
triggered.
1.
The
accumulated
runtime of
the indoor
fan exceeds
the alarm
threshold.
1.
Maintain or
replace the
indoor fan
and clear the
accumulated
runtime.
Indoor fan 4
exceed runtime
alarm
Warning
An alarm is
triggered.
1.
The
accumulated
runtime of
the indoor
fan exceeds
the alarm
threshold.
1.
Maintain or
replace the
indoor fan
and clear the
accumulated
runtime.
A023-01
Electric heater 1
fault
Major
An alarm is
triggered, and
the electric
heater is shut
down.
1.
The cables
to the
temperature
switch are
loose or
damaged.
2.
The
temperature
switch is
faulty.
3.
The manual
reset switch
is not reset.
4.
The electric
heater is
faulty.
1.
Check the
cables to the
temperature
switch.
2.
Maintain or
replace the
temperature
switch.
3.
Reset the
manual reset
switch.
4.
Replace the
electric
heater.
Electric heater 2
fault
Major
An alarm is
triggered, and
the electric
heater is shut
down.
1.
The cables
to the
temperature
switch are
loose or
damaged.
2.
The
temperature
switch is
faulty.
3.
The manual
1.
Check the
cables to the
temperature
switch.
2.
Maintain or
replace the
temperature
switch.
3.
Reset the
manual reset
switch.