NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
183
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
humidity sensor is faulty.
humidity sensor.
a113
Hot aisle
temp/humid
board comm
failed
Major
An alarm is
triggered.
1.
The cables to the T/H
sensor are loose or
damaged.
2.
The DIP switch of the T/H
sensor is set incorrectly.
3.
The T/H sensor is faulty.
4.
The communication port of
the control board is faulty.
1.
Check the cables to
the T/H sensor.
2.
Set the DIP switch of
the T/H sensor
correctly.
3.
Maintain or replace
the T/H sensor.
4.
Maintain or replace
the control board.
a117
Group units
number not
match
Major
The master
unit cannot
obtain the
smart
cooling
product data
from the
smart
module, and
the smart
cooling
product
cannot run in
iCooling
mode.
1.
Teamwork settings are
incorrect for slave units.
2.
The number of smart
cooling product units is
incorrectly set in the master
unit.
3.
A slave unit is offline.
1.
Modify teamwork
settings for slave units
to enable slave units
to join the teamwork
group.
2.
Set total number of
units on the master
unit to the actual
number of units.
3.
Check the cable
connection and
running conditions of
the slave units.
a118
Main power
off
Major
N/A
1.
The primary power supply
is faulty.
2.
The cables to the primary
power supply are loose or
damaged.
1.
Check the primary
power supply.
2.
Check the cables to
the primary power
supply.
a120
Indoor fan
1/2/3/4
communicat
ion failure
Major
N/A
1.
The indoor fan
communications cable is
not properly connected.
2.
The indoor fan is faulty.
1.
Check the
communications cable
connection to the
indoor fan.
2.
Maintain or replace
the indoor fan.
a130
Water inlet
solenoid
valve fault
alarm
Major
An alarm is
triggered,
and the
humidifier of
the smart
cooling
product is
shut down.
1.
The cables to the water inlet
solenoid valve are loose or
damaged.
2.
The water inlet solenoid
valve is faulty.
1.
Check the cables to
the water inlet
solenoid valve.
2.
Replace the water
inlet solenoid valve.
NOTE
After the fault is rectified,
click
Clear
on the alarm
page to manually clear the
alarm.
a167
Auxiliary
Major
An alarm is
The auxiliary power supply is
Replace the auxiliary