NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
55
2.
Move the cabinet onto the base. Secure the cabinet to the base using six bolts. Install a
shock pad between the base and the cabinet.
Shock absorption pads need to be attached to the top of the bases.
For a single-door and double-dour cabinet, tighten only the four screws at both sides.
Eight screws need to be tightened to secure a quadruple-door cabinet. Tighten the four
screws at both ends of the cabinet and one diagonal line of each of the two modules in the
middle.
Figure 3-23
Securing equipment
3.4.7 Lowering a Fan (Applicable To Downflow Units)
Context
Exercise caution when raising or lowering a fan to prevent personal injury.