NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
187
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
loss
configured)may be faulty.
the backup SPD.
a213
Backup
power
failure alarm
Major
N/A
1.
The backup power supply
voltage exceeds the upper
threshold.
2.
The backup SPD
three-phase detection board
is faulty.
1.
Check the backup
power supply voltage.
2.
Replace the backup
SPD three-phase
detection board.
a214
Backup
power A-B
line
overvoltage
alarm
Major
N/A
1.
The backup power supply
voltage exceeds the upper
threshold.
2.
The backup SPD
three-phase detection board
is faulty.
1.
Check the backup
power supply voltage.
2.
Replace the backup
SPD three-phase
detection board.
a215
Standby
power
AB/BC/CA
undervoltag
e
Major
N/A
1.
The backup power supply
voltage is below the lower
threshold.
2.
The cables to the backup
SPD three-phase detection
board are loose or damaged.
3.
The backup SPD
three-phase detection board
is faulty.
1.
Check the backup
power supply voltage.
2.
Check the cables to
the backup SPD
three-phase detection
board.
3.
Replace the backup
SPD three-phase
detection board.
a216
Standby
power
overfreq
Major
N/A
1.
The power supply
frequency is too high.
2.
The SPD three-phase test
board is faulty.
1.
Check the backup
power supply
frequency.
2.
Replace the backup
SPD three-phase test
board.
a217
Standby
power
underfreq
Major
N/A
1.
The power supply
frequency is too low.
2.
The SPD three-phase test
board is faulty.
1.
Check the backup
power supply
frequency.
2.
Replace the backup
SPD three-phase test
board.
a218
Standby
SPD 3-ph
test bd com
fault
Major
N/A
1.
The backup
communications cable is
loose or damaged.
2.
The backup SPD
three-phase detection board
is faulty.
3.
The communications port
of the main control board is
faulty.
1.
Check the backup
communications
cable.
2.
Replace the backup
SPD three-phase
detection board.
3.
Maintain or replace
the main control
board.
a219
Standby
SPD failed
Major
N/A
The backup SPD three-phase
detection board is faulty.
Replace the backup SPD
three-phase detection
board.