NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
4 Commissioning
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
131
Parameter
Description
Configuration Principle
controlled based on the
minimum data value collected
by the collector.
Temperature
setpoint
After the Temperature and humidity
control type and the temperature
value under this type are set, the
device conducts cooling or heating
based on the settings.
Set this parameter as required.
Return air temperature: 26–35°C
recommended
Supply air temperature:
18–24°C recommended
Cold aisle temperature: 18–24°C
recommended
Hot aisle temperature: 26–35°C
recommended
Humidity
setpoint
After the Temperature and humidity
control type and the humidity value
under this type are set, the device
conducts humidifying or
dehumidifying based on the
settings.
Set this parameter as
required.40%–60% RH
recommended
----End
4.4.2 (Optional) Setting the Pressure Difference Control
Prerequisites
If the differential pressure sensors are installed, perform the following operations accordingly.
If the differential pressure sensors are not installed, skip this part.
Procedure
Step 1
On the home screen, choose
Settings
>
System Settings
>
Indoor fan
, set
Air-side
difference pressure sensor type
to
0~500 Pa
.
Step 2
Set
Indoor fan control type
to
Pressure diff ctrl
.
Step 3
Change the other parameters based on the following instructions.
Table 4-5
Parameter description
Parameter
Description
Configuration Principle
Indoor fan control type
Sets the control type for the
indoor fan.
Normally, retain
R/S air
temp diff rate ctrl
. If the
differential pressure sensors
are configured, change to
Pressure diff ctrl
.
Indoor fan pressure
Sets the value for the
The default value is 10 Pa.