NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
65
3.5.2.1 Upflow
3.5.2.1.1 Bottom Pipe Routing
Prerequisites
Tools: 75# open-end wrench, 36# open-end wrench, 18# pipe wrench, sealant (used for
pasting thermal insulation foam), screw thread sealant.
Context
If the cabinets are not placed abreast onsite, you are advised to route the pipes from one side
of the cabinets.
Procedure
Step 1
To avoid deforming the pipe, use a 75# open-end wrench to fix the pipe nut, use a 36#
open-end wrench to fix the plug, and then remove the plug, as shown by (1) in
Figure 3-34
Installing Pipes
Step 2
Apply thread sealant evenly on the joints of external screw threads, and install the pipes from
inside out, as shown by (2) in
Step 3
Use a 75# open-end wrench and 18# pipe wrench to fix the pipe, as shown by (3) in