NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
211
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
is stuck or
faulty.
replace the
chilled water
valve.
A093-01
High humidity
alarm
Warning
N/A
1.
The thermal
load power
is low.
2.
The ambient
humidity
exceeds the
upper
threshold.
3.
The
temperature
and
humidity
sensor is not
installed in a
proper
position.
4.
The high
humidity
alarm
threshold is
inappropriat
e.
5.
The value
detected by
the
temperature
and
humidity
sensor is
different
from the
actual value.
1.
Contact
Huawei
technical
support.
2.
Measure the
ambient
humidity.
3.
Adjust the
position of
the
temperature
and
humidity
sensor.
4.
Adjust the
high
humidity
alarm
threshold.
5.
Calibrate or
replace the
temperature
and
humidity
sensors.
A094-01
Low humidity
alarm
Warning
N/A
1.
The ambient
humidity is
below the
lower
threshold.
2.
The
temperature
and
humidity
sensor is not
installed in a
proper
position.
3.
The low
humidity
1.
Measure the
ambient
humidity.
2.
Adjust the
position of
the
temperature
and
humidity
sensor.
3.
Adjust the
low
humidity
alarm
threshold.