NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
189
Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
is faulty.
3.
The threshold of fresh air
filter blockage set on the
differential pressure switch
is inappropriate.
4.
The pressure tube of the
differential pressure switch
of the fresh air unit is
blocked or disconnected.
5.
The cable to the differential
pressure switch of the fresh
air unit is not properly
connected.
6.
The direct free-cooling
plenum is faulty.
7.
The direct free-cooling
plenum is not enabled.
switch of the fresh air
unit.
3.
Adjust the threshold
set on the differential
pressure switch.
4.
Dredge or replace the
pressure tube.
5.
Check the cable
connection to the
differential pressure
switch of the fresh air
unit.
6.
Maintain or replace
the direct free-cooling
plenum.
7.
Enable the direct
free-cooling plenum.
Table 6-5
Alarm description (V200R002 software version)
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
A001-01
Supply air 1
temperature
sensor fault
Major
N/A
1.
The cables
to the
temperature
sensor are
loose or
damaged.
2.
The
temperature
sensor is
faulty.
3.
The cables
to the
temperature
and
humidity
sensor are
loose or
damaged.
4.
The
temperature
and
humidity
sensor is
faulty.
1.
Check the
cables to the
temperature
sensor.
2.
Maintain or
replace the
temperature
sensor.
3.
Check the
cables to the
temperature
and
humidity
sensor.
4.
Maintain or
replace the
temperature
and
humidity
sensor.