NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
231
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
liquid level
sensor,
check its
cable
connections,
clear the
obstacles, or
replace it.
A27F-02
Water overflow
alarm
Critical
An alarm is
triggered, and
all the parts
expect for
indoor fans are
shut down.
The water
overflow sensor
detects water or
the sensor is
faulty.
While
configuring the
water overflow
sensor, check
and clear the
water source,
and maintain or
replace the
sensor.
A280-01
Power
frequency
abnormal
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the main
power or single
power is
supplied.
1.
The power
supply
frequency is
below the
lower
threshold.
2.
The SPD
and voltage
detection
board is
faulty.
1.
Check that
the power
supply
voltage is
within the
operating
range.
2.
Replace the
SPD and
voltage
detection
board.
Backup power
frequency
abnormal
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the
standby power
is supplied.
1.
The power
supply
frequency is
below the
lower
threshold.
2.
The SPD
and voltage
detection
board is
faulty.
1.
Check that
the power
supply
voltage is
within the
operating
range.
2.
Replace the
SPD and
voltage
detection
board.
A280-02
Power
frequency
abnormal
Major
An alarm is
triggered, and
the smart
cooling product
is shut down
when the main
power or single
power is
1.
The power
supply
frequency
exceeds the
upper
threshold.
2.
The SPD
and voltage
detection
1.
Check that
the power
supply
voltage is
within the
operating
range.
2.
Replace the
SPD and