22
Features
The controller provides a touchscreen with a user-friendly interface.
The controller controls the indoor temperature precisely and responds quickly.
The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
The controller provides multiple protection functions, such as overvoltage/undervolatge
protection, abnormal power-off self-recovery, and water leakage detection, ensuring
system reliability.
The controller displays the operating status and duration of the smart cooling product
components in real time.
The expert system automatically displays the information of the current fault, which
facilitates the maintenance.
The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism.
The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.
2.4 Monitoring System
The monitoring system provides logic control, data collection, control demand delivering,
alarm reporting, data storage, user right management, and teamwork control. You can connect
the smart cooling product monitoring system to your monitoring system over a northbound
communications port to perform remote management. The smart cooling product supports
remote monitoring ports and provides RS485 ports and FE ports to support Modbus-RTU,
Modbus-TCP and SNMP for real-time data collection and alarm reporting.
Smart cooling products can be networked over the CAN bus to realize teamwork control,
energy conservation, and service life extension.
2.5 Operating Conditions
If the water inlet temperature exceeds 10°C or the total load is less than 30% of the cooling
capacity of a single smart cooling product, the humidity may be high. The customer is advised
to add a dehumidifier (engineering procurement).