NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
31
Figure 3-2
Layout of bottom pipe routing (2)
(1) NetCol8000-C
The height of raised floors is greater than 800 mm.
L indicates the front maintenance distance, and the minimum L is 900 mm. If this requirement
cannot be met, the minimum L after front doors are removed can be 800 mm.
Figure 3-3
Layout of side pipe routing
(1) NetCol8000-C