NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
201
Alarm ID
Alarm Name
Alarm
Severity
Impact
Possible
Cause
Solution
loose or
damaged.
6.
The air
damper for
the air filter
is faulty.
7.
The air
damper for
the air filter
is not
enabled
for the air
filter.
Fresh air filter
blocked alarm
Warning
An alarm is
triggered, and
the electric
heater and
humidifier of
the smart
cooling product
are shut down.
1.
Air filters
are blocked
or dirty.
2.
The
differential
pressure
switch is
faulty.
3.
The
threshold set
for the
differential
pressure
switch is
inappropriat
e.
4.
The pressure
tube of the
differential
pressure
switch is
blocked or
disconnected
.
5.
The cables
to the
differential
pressure
switch are
loose or
damaged.
6.
The air
damper for
the air filter
is faulty.
7.
The air
damper for
the air filter
is not
1.
Maintain or
replace the
air filters.
2.
Replace the
differential
pressure
switch.
3.
Adjust the
threshold set
for the
differential
pressure
switch.
4.
Dredge or
replace the
pressure
tube.
5.
Check the
cables to the
differential
pressure
switch.
6.
Maintain or
replace the
air damper
for the air
filter.
7.
Enable the
air damper
for the air
filter.