NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
3 Installation Guide
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
105
For details about how to connect the motorized damper, see the documents delivered with it.
3.6.9 (Optional) Connecting the T/H Sensor Outside the Cabinet
Context
T/H sensors outside the cabinet are configured to detect the temperatures of cold/hot aisles.
They can be flexibly installed on the server cabinet based on site situations. It is
recommended that the T/H sensors be deployed near heat sources in the hot aisle, or in places
which lacks cooling air in the cold aisle. Place the T/H sensors on the cabinet adjacent to the
smart cooling product without directly facing the exhaust vents of the smart cooling product.
Procedure
Step 1
Connect the T/H sensors outside the cabinet and the T/H sensors at the return air side in
series.
Figure 3-77
Upflow