NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
6 System Operation and Maintenance
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
258
Exercise caution because the device is still energized when it is shut down over the LCD.
Step 2
Open the front door and turn off the general switch. For a device that has two power inputs,
turn off the active power switch QF1 and standby power switch QF2. Then, remove the fan
maintenance cover using a Phillips screwdriver.
Figure 6-21
Removing the fan maintenance baffle plate
Step 3
Remove screws that secure the fan and the fan support using a 13# socket wrench.