Alar
m ID
Alarm
Name
Alarm
Severi
ty
Impact
Possible Cause
Solution
system is
shut down.
2.
The SPD three-phase
detection board is faulty.
range.
2.
Replace the SPD
three-phase detection
board.
a029
Power BC
overvoltage
Major
An alarm is
triggered,
and the
system is
shut down.
1.
The power supply voltage
exceeds the upper
threshold.
2.
The SPD three-phase
detection board is faulty.
1.
Check the power
supply voltage, and
ensure that the voltage
is within the operating
range.
2.
Replace the SPD
three-phase detection
board.
a030
Power CA
overvoltage
Major
An alarm is
triggered,
and the
system is
shut down.
1.
The power supply voltage
exceeds the upper
threshold.
2.
The SPD three-phase
detection board is faulty.
1.
Check the power
supply voltage, and
ensure that the voltage
is within the operating
range.
2.
Replace the SPD
three-phase detection
board.
a031
Power AB
undervoltag
e
Major
An alarm is
triggered,
and the
system is
shut down.
1.
The power supply voltage is
below the lower threshold.
2.
The cables to the SPD
three-phase detection board
are loose or damaged.
3.
The SPD three-phase
detection board is faulty.
1.
Check the power
supply voltage.
2.
Check the cables to
the SPD three-phase
detection board.
3.
Replace the SPD
three-phase detection
board.
a032
Power BC
undervoltag
e
Major
An alarm is
triggered,
and the
system is
shut down.
1.
The power supply voltage is
below the lower threshold.
2.
The cables to the SPD
three-phase detection board
are loose or damaged.
3.
The SPD three-phase
detection board is faulty.
1.
Check the power
supply voltage.
2.
Check the cables to
the SPD three-phase
detection board.
3.
Replace the SPD
three-phase detection
board.
a033
Power CA
undervoltag
e
Major
An alarm is
triggered,
and the
system is
shut down.
1.
The power supply voltage is
below the lower threshold.
2.
The cables to the SPD
three-phase detection board
are loose or damaged.
3.
The SPD three-phase
detection board is faulty.
1.
Check the power
supply voltage.
2.
Check the cables to
the SPD three-phase
detection board.
3.
Replace the SPD
three-phase detection
board.
a034
Power
overfreq
Major
An alarm is
triggered,
and the
1.
The power supply
frequency exceeds the
upper threshold.
1.
Check the power
supply frequency, and
ensure that it is within