NetCol8000-C(070-260) In-room Chilled Water Smart
Cooling Product
User Manual
7 FAQ
Issue 06 (2020-01-13)
Copyright © Huawei Technologies Co., Ltd.
282
Figure 7-8
Screen displayed when the calibration is complete
Calibrating the screen by DIP switch.
a.
Flip toggle switch 1 for the display to ON, and others to the opposite position, and
wait for 3 seconds before calibrating.
b.
Flip the fourth toggle switch to ON and others remain unchanged. The screen
calibration function is triggered.
After 15 seconds, a dialog box indicating
Are you sure you want to calibrate the
screen? If you do not click Confirm or Cancel, calibration will start
automatically 10s later.
is displayed.
c.
Wait for 10 seconds or tap
Confirm
is displayed. Tap the screen. When
is displayed, the adjustment is complete.
d.
Flip toggle switch 1 for the display to ON, and others to the opposite position.
After the DIP switch is calibrated, flip toggle switch 1 to ON, and others to the opposite position.
You need to manually operate the operation again from the first step to trigger the touchscreen
calibration function after the calibration failure.
----End
7.1.13 How to Modify a Password
Prerequisites
To modify a password, log in as the
admin
user or
operator
user.
You can only modify the password of the current user.
Procedure
Step 1
On the home screen, choose
Settings
>
User Settings
to enter the
User Settings
screen, as