122
Learning Basic Features
Code
Description
ADV-03 Acc S Start
Sets the gradient level as acceleration starts when using an S-curve, Acc/Dec
pattern. ADV-03 defines S-curve gradient level as a percentage, up to half of
total acceleration.
If the frequency reference and maximum frequency are set at 60 Hz and ADV-
03 is set to 50%, ADV-03 configures acceleration up to 30 Hz (half of 60 Hz). The
inverter will operate S-curve acceleration in the 0-15 Hz frequency range (50%
of 30 Hz). Linear acceleration will be applied to the remaining acceleration
within the 15–30 Hz frequency range.
ADV-04 Acc S End
Sets the gradient level as acceleration ends when using an S-curve Acc/Dec
pattern. ADV-03 defines S-curve gradient level as a percentage, above half of
total acceleration.
If the frequency reference and the maximum frequency are set at 60 Hz and
ADV-04 is set to 50%, setting ADV-04 configures acceleration to increase from
30 Hz (half of 60 Hz) to 60 Hz (end of acceleration). Linear acceleration will be
applied within the 30-45 Hz frequency range. The inverter will perform an S-
curve acceleration for the remaining acceleration in the 45–60 Hz frequency
range.
ADV-05 Dec S Start –
ADV-06 Dec S End
Sets the rate of S-curve deceleration. Configuration for codes ADV-05 and
ADV-06 may be performed the same way as configuring codes ADV-03 and
ADV-04.
[Acceleration / deceleration pattern configuration]
S
-curve
Linear
Acc. time
Dec. time
Frequency
Run cmd
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...