140
Learning Basic Features
4.18.3
Frequency Jump
Use frequency jump to avoid mechanical resonance frequencies. The inverter will avoid identified
ranges during acceleration and deceleration. Operation frequencies cannot be set within the pre-
set frequency jump band.
When a frequency setting is increased, while the frequency parameter setting value (voltage,
current, RS-485 communication, keypad setting, etc.) is within a jump frequency band the
frequency will be maintained at the lower limit value of the frequency band. Then, the frequency
will increase when the frequency parameter setting exceeds the range of frequencies used by the
frequency jump band.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
ADV
27
Frequency jump
Jump Freq
00–1
0–1
-
28
Jump frequency
lower limit1
Jump Lo 1
10.00
0.00–Jump frequency
upper limit 1
Hz
29
Jump frequency
upper limit1
Jump Hi 1
15.00
Jump frequency lower
limit 1–Maximum
frequency
Hz
30
Jump frequency
lower limit 2
Jump Lo 2
20.00
0.00–Jump frequency
upper limit 2
Hz
31
Jump frequency
upper limit 2
Jump Hi 2
25.00
Jump frequency lower
limit 2–Maximum
frequency
Hz
32
Jump frequency
lower limit 3
Jump Lo 3
30.00
0.00–Jump frequency
upper limit 3
Hz
33
Jump frequency
upper limit 3
Jump Hi 3
35.00
Jump frequency lower
limit 3–Maximum
Hz
ADV-33
ADV-32
ADV-31
ADV-30
ADV-29
ADV-28
10V V1
20mA I
0
(voltage input)
(current input)
when the frequency reference decreases
Run cmd
Frequency
when the frequency reference increases
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...