87
Learning Basic Features
Mode
Description
set at DRV-25 (HAND Cmd Freq).
1 Follow Auto The inverter takes over the operation direction and the
frequency reference from the settings for AUTO mode and
keeps performing the same operation. If the inverter was
stopped in AUTO mode, the operation direction is set as Fx
and the frequency reference is set as 0 (no inverter output).
2
HAND
AUTO
Press the AUTO key in HAND mode to switch to AUTO mode. The inverter
operates based on the command source and frequency reference settings set at
DRV-06 and DRV-07. If DRV-06 (Cmd Source) is set to ‘keypad’ press the AUTO key
once again to start inverter operation.
3
AUTO
OFF
Press the OFF key in AUTO mode to stop the inverter operation (the inverter
enters OFF mode).
4
OFF
AUTO
Press the AUTO key in OFF mode to switch to AUTO mode. The inverter operates
based on the command source and frequency reference settings set at DRV-06
and DRV-07. If DRV-06 (Cmd Source) is set to ‘keypad’ press the AUTO key once
again to start inverter operation.
5
HAND
OFF
Press the OFF key in HAND mode to stop the inverter operation (the inverter
enters OFF mode).
6
OFF
HAND
Press the HAND key in OFF mode to switch to HAND mode. The inverter operates
based on the operation direction set at DRV-02 (Keypad Run Dir) and the
frequency reference set at DRV-25 (HAND Cmd Freq).
Operation Mode at Power Recovery
If a power interruption occurs during inverter operation in the OFF or HAND mode, the inverter
halts the operation with low voltage fault trip. Then, when the power is recovered, the inverter
turns on in OFF mode.
If the inverter was operating in AUTO mode at the time of the low voltage trip following the power
interruption, the inverter turns on in AUTO mode, and the operation may vary depending on the
inverter’s ‘PowerOn Resume’ and ‘Power-on run’ settings.
Note
•
To operate the inverter using the keypad in AUTO mode, set DRV-06 (CMD Source) to
‘KeyPad’ and press the AUTO key to enter AUTO mode. Then, press the AUTO key on the
keypad once again to start the inverter operation.
•
If a fault trip occurs during an operation in the AUTO or HAND mode, the inverter can be
reset by pressing the OFF key. After the reset, the fault trip is released and the inverter enters
Summary of Contents for 6731001500
Page 1: ......
Page 17: ...Preparing the Installation 4 37 90kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500kW 3 Phase ...
Page 34: ...21 Installing the Inverter 400 V 220 500kW ...
Page 50: ...37 Installing the Inverter Inputand OutputControlTerminalBlockWiringDiagram 5 5 90kW ...
Page 66: ...Perform BasicOperations 53 ...
Page 106: ...93 Learning BasicFeatures 0 10V InputVoltageSettingDetails V1 Quantizing ...
Page 107: ...94 Learning BasicFeatures ...
Page 187: ...174 Learning Advanced Features PIDCommandBlock ...
Page 188: ...175 Learning Advanced Features ...
Page 189: ...176 Learning Advanced Features PIDFeedbackBlock ...
Page 190: ...177 Learning Advanced Features PIDOutputBlock ...
Page 191: ...178 Learning Advanced Features PIDOutputModeBlock ...
Page 205: ...192 Learning Advanced Features EPID1Controlblock ...
Page 206: ...193 Learning Advanced Features EPID2Controlblock ...
Page 228: ...215 Learning Advanced Features ...
Page 244: ...231 Learning Advanced Features TheTime Chartfor the Exception Day ...
Page 260: ...247 Learning Advanced Features SpeedSearchOperation SettingDetails ...
Page 405: ...392 RS 485 Communication Features 7 3 9 2 Control Area Parameter Read Write ...
Page 555: ...Table ofFunctions 542 8 16 4 CoolingTower MC4 Group ...
Page 558: ...Tableof Functions 545 8 16 5 Circulation Pump MC5 Group ...
Page 562: ...Tableof Functions 549 8 16 6 Vacuum Pump MC6 Group ...
Page 588: ...575 Troubleshooting ...
Page 608: ...TechnicalSpecification 595 11 3 External Dimensions 0 75 30kW 3 phase 37 90kW 3 phase ...
Page 609: ...TechnicalSpecification 596 110 185kW 3 phase ...
Page 632: ...TechnicalSpecification 619 400 V 37 500 kW Current Derating Rate ...
Page 643: ...630 ...
Page 644: ...631 ...
Page 645: ...632 ...